Text or email this page to your electrician before rough-in.
NIGHTJAR SAUNA
Outdoor Saunas & Cold Plunges · Grand Rapids, MI
Electrical Cut Sheet
Rough-in & branch circuit spec
Heater
IKI Pillar — 9 kW UL 875
Control
HUUM UKU Wi-Fi Glass
Service
240V · 1-Phase 60 Hz
Branch Circuit — Heater Power Feed
| Connected Load | 9 kW |
| Voltage / Phase | 240V, single-phase, 60 Hz |
| Full-Load Current | 37.5 A |
| Overcurrent Protection | 50 A, 2-pole breaker — dedicated circuit |
| Branch Conductors | #6/3 w/ ground copper — L1, L2, Neutral + equipment ground |
| Neutral — Required | Powers the UKU control unit (120V L-N) and any 120V aux (lighting). Not optional — module won't run without it. |
| Equipment Ground | #10 AWG copper min. (NEC 250.122, 50A). Separate from neutral — no bonding at heater or module. |
| Conductor Rating | 90°C (194°F) copper. No PVC-insulated cable inside the sauna — thermal embrittlement. |
| High-Heat Runs | Cable run > 1000 mm above floor inside the wall must withstand 170°C / 338°F. |
| Connection Method | Permanent hardwire in seal-tight conduit. No plugs or receptacles inside the sauna enclosure. |
Control — HUUM UKU Wi-Fi (Glass)
| Switching Capacity | Main module switches up to 9 kW direct — no extension box or contactor for this build. |
| Power Routing | Branch feed (L1/L2/N + gnd) lands in the UKU main module at input terminals L1 L2 N. Neutral terminates here — it does not go to the heater. Module output (V/U) feeds the heater: L1, L2 + ground only, 240V. Heater leg carries full load — #6 Cu / 90°C. |
| Main Module Location | Mount in a dry, accessible spot outside the hot enclosure. Not inside the sauna. |
| Glass Panel | Low-voltage panel cable to module (3 m, 4 × 0.34 mm²). Recessed or surface mount. |
| Temperature Sensor | Mounted in sauna per HUUM placement; wired to module. Built-in overheat cutoff (130°C). |
| Connectivity | 2.4 GHz Wi-Fi at the module for HUUM app / remote start. |
Install Notes
- All electrical by a licensed electrician to NEC + local code.
- Heater feed is continuous-load sized: 50A / #6 covers the 125% rule and voltage drop on long runs.
- Bond heater and module grounds to provided terminals.
- Outdoor build — confirm the circuit originates from a suitably protected exterior-rated source and disconnect.
Verify On Site
- 240V single-phase confirmed at panel (not 208V).
- Breaker space for a 2-pole 50A.
- Run length — upsize for voltage drop past ~60 ft.
- GFCI / disconnect per local AHJ for the outdoor location.
If it's a 208V or 3-phase job — amperage, breaker, and conductor sizing change. This sheet is 240V single-phase only. Flag it before rough-in and pull the revised spec.
NIGHTJAR SAUNA · Grand Rapids, MI · Outdoor saunas & cold plunges
Reference values from IKI (UL 875) and HUUM UKU installation manuals. Provided as a rough-in guide — final design, sizing, and inspection are the responsibility of the installing licensed electrician per NEC and local code. Rev. Aug 2026.